Schneider Electric Modicon PLCs Predictable Value Range from Previous Values

CVE-2017-6030

Assigned byThe organization (CNA) that assigned this CVE ID and published the record, usually the vendor.
ICS-CERT (opens in new tab)
Published
Last modified
NVD status
Modified
CVSS 3.16.5Medium

Description

A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.

Exploitation

Whether attackers are exploiting this vulnerability, and how likely they are to try in the next 30 days.

CISA SSVC assessmentAbout SSVC (opens in new tab)

CISA's assessment of whether it's exploited, whether attacks can be automated and how much control an attacker gains.

ExploitationWhether CISA has seen exploit code or attacks for this vulnerability.
None known
AutomatableWhether attackers can exploit it at scale without manual steps.
Yes
Technical impactHow much control of the affected system an attacker gains.
Partial control
Assessed

FIRST Exploit Prediction Scoring System (EPSS)About EPSS (opens in new tab)

FIRST's estimate of the chance attackers try to exploit this vulnerability in the next 30 days.

Probability of exploitationIt predicts attempts, not success, and is updated daily.
2.184%
Compared with other CVEs
At or above 82.733% of scored CVEs
Scored

Affected products

The products and versions with the vulnerability.

Listed by CNA

The products and versions affected, according to the organization that published this CVE.

VendorProductAffected versions
Schneider ElectricModicon M221
  • < 1.5.0.0
Schneider ElectricModicon M241
  • < 4.0.5.11
Schneider ElectricModicon M251
  • < 4.0.5.11

How to fix the vulnerability, or reduce the risk until you can.

Solutions

From ICS-CERT, which published this CVE.

Schneider Electric has released new firmware versions to address the predictable value range from previous values vulnerability and the use of insufficiently random values vulnerability, which are available through Schneider Electric’s software update tool, SoMachine, Version 4.2, and SoMachineBasic, Version 1.5. Schneider Electric has not released a product to address the insufficiently protected credentials vulnerability; however, Schneider Electric has provided compensating controls to reduce the risk of exploitation.

SoMachineBasic, Version 1.5, is available at the following location:

http://www.schneider-electric.fr/fr/download/document/SOMBASAP15SOFT/ 

Schneider Electric has provided the following compensating controls to reduce the risk of exploitation of the insufficiently protected credentials vulnerability:

  • Verify that the hardware and software infrastructure that the PLCs are integrated into (along with all organizational measures and rules covering access to the infrastructure) consider the results of the hazard and risk analysis, and are implemented according to best practices and standards such as ISA/IEC 62443.
  • Limit traffic on the local network with managed switches
  • Where possible, avoid using Wi-Fi networks, but when Wi-Fi is essential, use only secure communications (such as WPA2 encryption)
  • Do not grant [network] access to unknown computers
  • When remote access is essential, use secure methods such as Virtual Private Networks (VPNs), and ensure the remote access solution(s), as well as the remote computer(s) are kept up-to-date with the latest security patches.

Schneider Electric has released Security Notifications SEVD-2017-075-01, SEVD-2017-075-02, and SEVD-2017-075-03, which provide additional information about the identified vulnerabilities, mitigations, and compensating controls:

http://www.schneider-electric.com/en/download/document/SEVD-2017-075-01/

http://www.schneider-electric.com/en/download/document/SEVD-2017-075-02/

http://www.schneider-electric.com/en/download/document/SEVD-2017-075-03/

Severity

How serious the vulnerability is if exploited, scored from 0 to 10 with the CVSS standard (opens in new tab).

  • 6.5 MediumCVSS 3.1 · PrimaryPrimary scores are NVD's own. Secondary scores come from the organization that published the CVE, or from CISA. · Scored by NVD (opens in new tab)
    Attack vectorWhere the attacker has to be. Network is the widest: anywhere on the Internet.
    Network
    Attack complexityWhether the attack depends on conditions the attacker doesn't control.
    Low
    Privileges requiredThe access the attacker needs before attacking.
    None
    User interactionWhether someone other than the attacker has to do something, like open a link.
    None
    ScopeWhether the attack can reach beyond the vulnerable component.
    Unchanged
    ConfidentialityHow much data the attacker can read.
    None
    IntegrityHow much data the attacker can change.
    Low
    AvailabilityHow much the attacker can disrupt the system or service.
    Low

    CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:LView in FIRST's calculator (opens in new tab)

  • 6.5 MediumCVSS 3.1 · SecondaryPrimary scores are NVD's own. Secondary scores come from the organization that published the CVE, or from CISA. · Scored by CISA (opens in new tab)
    Attack vectorWhere the attacker has to be. Network is the widest: anywhere on the Internet.
    Network
    Attack complexityWhether the attack depends on conditions the attacker doesn't control.
    Low
    Privileges requiredThe access the attacker needs before attacking.
    None
    User interactionWhether someone other than the attacker has to do something, like open a link.
    None
    ScopeWhether the attack can reach beyond the vulnerable component.
    Unchanged
    ConfidentialityHow much data the attacker can read.
    None
    IntegrityHow much data the attacker can change.
    Low
    AvailabilityHow much the attacker can disrupt the system or service.
    Low

    CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:LView in FIRST's calculator (opens in new tab)

  • 6.4 MediumCVSS 2.0 · PrimaryPrimary scores are NVD's own. Secondary scores come from the organization that published the CVE, or from CISA. · Scored by NVD (opens in new tab)
    Attack vectorWhere the attacker has to be. Network is the widest: anywhere on the Internet.
    Network
    Attack complexityWhether the attack depends on conditions the attacker doesn't control.
    Low
    AuthenticationHow many times the attacker has to sign in.
    None
    ConfidentialityHow much data the attacker can read.
    None
    IntegrityHow much data the attacker can change.
    Partial
    AvailabilityHow much the attacker can disrupt the system or service.
    Partial

    AV:N/AC:L/Au:N/C:N/I:P/A:PView in NVD's calculator (opens in new tab)

Weaknesses and attack patterns

The type of bug behind the vulnerability, and how attackers exploit that type.

  • Predictable Value Range from Previous Values · CWE-343 (opens in new tab)

    The product's random number generator produces a series of values which, when observed, can be used to infer a relatively small range of possibilities for the next value that could be generated.

    Abstraction
    Base
    Mapping guidance
    Allowed
    Part of
  • Insufficient Entropy · CWE-331 (opens in new tab)

    The product uses an algorithm or scheme that produces insufficient entropy, leaving patterns or clusters of values that are more likely to occur than others.

    Abstraction
    Base
    Mapping guidance
    Allowed
    Part of

References

Advisories, patches, exploits and more about this vulnerability.

This product uses the NVD API but is not endorsed or certified by the NVD (opens in new tab). CVE records from the CVE List (opens in new tab), weakness types from MITRE's CWE (opens in new tab)™ and attack patterns from its CAPEC (opens in new tab)™ are © The MITRE Corporation, used under the CVE (opens in new tab), CWE (opens in new tab) and CAPEC (opens in new tab) terms of use. Known exploited vulnerabilities and SSVC assessments are from CISA. Exploit predictions are from FIRST's EPSS (opens in new tab). About this data