GE Hydran M2 Predictable Value Range from Previous Values

CVE-2014-5409

Assigned byThe organization (CNA) that assigned this CVE ID and published the record, usually the vendor.
ICS-CERT (opens in new tab)
Published
Last modified
NVD status
Modified
CVSS 2.05Medium

Description

The 17046 Ethernet card before 94450214LFMT100SEM-L.R3-CL for the GE Digital Energy Hydran M2 does not properly generate random values for TCP Initial Sequence Numbers (ISNs), which makes it easier for remote attackers to spoof packets by predicting these values.

Exploitation

Whether attackers are exploiting this vulnerability, and how likely they are to try in the next 30 days.

FIRST Exploit Prediction Scoring System (EPSS)About EPSS (opens in new tab)

FIRST's estimate of the chance attackers try to exploit this vulnerability in the next 30 days.

Probability of exploitationIt predicts attempts, not success, and is updated daily.
2.718%
Compared with other CVEs
At or above 86.387% of scored CVEs
Scored

Affected products

The products and versions with the vulnerability.

Listed by CNA

The products and versions affected, according to the organization that published this CVE.

VendorProductAffected versions
GEHydran M2, containing the 17046 Ethernet option
  • < October 2014

How to fix the vulnerability, or reduce the risk until you can.

Solutions

From ICS-CERT, which published this CVE.

GE Digital Energy has released a new version of the Ethernet option,
which resolves the identified vulnerability in newly released Hydran M2
devices. The update changes the sequence algorithm, which makes it
improbable that a TCP sequence attack could succeed. The version of
Ethernet card that implements this improvement is
94450214LFMT100SEM-L.R3-CL.

Workarounds

From ICS-CERT, which published this CVE.

There is no method to update Hydran M2 devices released prior to
October 2014. GE Digital Energy recommends that utilities using older
versions of the Hydran M2 device implement network security defensive
measures, to include the following:

•     Place the Hydran M2 inside the control system network security perimeter with access controls and monitoring.

•     Minimize network exposure to all other control system devices.
Control system devices should not directly face the Internet or business
networks.

•     Locate control system networks and devices behind properly
configured firewalls, and isolate them from the business network.

•     When remote access is required, use secure methods, such as
Virtual Private Networks (VPNs), recognizing that VPNs may have
vulnerabilities and should be updated to the most current version
available. Also recognize that VPN is only as secure as the connected
devices.

GE Digital Energy’s Product Bulletin is available in at the following location, with a user account:

http://libraries.ge.com/download?fileid=642886573101&entity_id=31955841101&sid=101

Severity

How serious the vulnerability is if exploited, scored from 0 to 10 with the CVSS standard (opens in new tab).

  • 5 MediumCVSS 2.0 · PrimaryPrimary scores are NVD's own. Secondary scores come from the organization that published the CVE, or from CISA. · Scored by NVD (opens in new tab)
    Attack vectorWhere the attacker has to be. Network is the widest: anywhere on the Internet.
    Network
    Attack complexityWhether the attack depends on conditions the attacker doesn't control.
    Low
    AuthenticationHow many times the attacker has to sign in.
    None
    ConfidentialityHow much data the attacker can read.
    Partial
    IntegrityHow much data the attacker can change.
    None
    AvailabilityHow much the attacker can disrupt the system or service.
    None

    AV:N/AC:L/Au:N/C:P/I:N/A:NView in NVD's calculator (opens in new tab)

  • 6.4 MediumCVSS 2.0 · SecondaryPrimary scores are NVD's own. Secondary scores come from the organization that published the CVE, or from CISA. · Scored by ICS-CERT (opens in new tab)
    Attack vectorWhere the attacker has to be. Network is the widest: anywhere on the Internet.
    Network
    Attack complexityWhether the attack depends on conditions the attacker doesn't control.
    Low
    AuthenticationHow many times the attacker has to sign in.
    None
    ConfidentialityHow much data the attacker can read.
    Partial
    IntegrityHow much data the attacker can change.
    None
    AvailabilityHow much the attacker can disrupt the system or service.
    Partial

    AV:N/AC:L/Au:N/C:P/I:N/A:PView in NVD's calculator (opens in new tab)

Weaknesses and attack patterns

The type of bug behind the vulnerability, and how attackers exploit that type.

  • Predictable Value Range from Previous Values · CWE-343 (opens in new tab)

    The product's random number generator produces a series of values which, when observed, can be used to infer a relatively small range of possibilities for the next value that could be generated.

    Abstraction
    Base
    Mapping guidance
    Allowed
    Part of

References

Advisories, patches, exploits and more about this vulnerability.

This product uses the NVD API but is not endorsed or certified by the NVD (opens in new tab). CVE records from the CVE List (opens in new tab), weakness types from MITRE's CWE (opens in new tab)™ and attack patterns from its CAPEC (opens in new tab)™ are © The MITRE Corporation, used under the CVE (opens in new tab), CWE (opens in new tab) and CAPEC (opens in new tab) terms of use. Known exploited vulnerabilities and SSVC assessments are from CISA. Exploit predictions are from FIRST's EPSS (opens in new tab). About this data